The MPS® Evolution III detection system is designed according to current standards and ensures the detection of CO, NO, NO₂, H₂, NH₃, H₂S, O₂, CO₂, and LPG in combination with addressable gas detectors for toxic and combustible gases.
The system offers extensive functionalities and configuration options, which can be set and managed directly on the MPS® Evolution III via a menu-driven TFT display or remotely via an external computer.
Downloads
- Datasheet NL
- Datasheet EN
- Handleiding (Revisie 2-2025)
- Installatie handleiding (Revisie 2-2025)
- Handleiding NL (Revisie augustus 2026)
- Aansluitschema industrie NL
- Aansluitschema Parkeer Garage NL
- Controlelijst NL
- Installatie Handleiding NL (Revisie augustus 2026)
- Manual EN (Revision August 2026)
- Verkorte_Handleiding NL (Revisie augustus 2026)
Details
The MPS® Evolution III detection system is designed according to current standards and ensures the detection of CO, NO, NO₂, H₂, NH₃, H₂S, O₂, CO₂, and LPG in combination with addressable gas detectors for toxic and combustible gases.
The system offers extensive functionalities and configuration options, which can be set and managed directly on the MPS® Evolution III via a menu-driven TFT display or remotely via an external computer.
64 DETECTORS ON A SINGLE CONTROL UNIT
Connection via Ethernet makes remote configuration and data provision simple. The system is suitable for monitoring up to 64 detectors, which can be connected randomly via an RS 485 serial data bus. For data processing, the MPS® Evolution III uses advanced technology, allowing external relay modules to be included in the loop. This increases system flexibility, as the modules can be placed in different rooms.
SAVINGS IN CABLING COSTS
The system's logic results in significantly reduced cabling costs, leading to economical installation. The MPS® Evolution III is supplied in a plastic wall-mounted enclosure with 8 freely configurable standard relays and 4 discrete inputs for connecting external input signals. The enclosure has space for an additional relay module, which also includes 8 freely configurable relays.
An optional battery backup system (UPS) is available.
Since many older systems are based on star wiring, the design has been developed to convert this into an addressable loop, often allowing existing cabling to be reused.
APPLICATION
The MPS® Evolution III is designed for use in parking and storage garages where mechanical ventilation control is required.
The gas detection system activates the ventilation system in the event of elevated CO, NO, or LPG concentrations. It also initiates the activation of the evacuation system and the connection to the fire alarm control panel. The MPS® Evolution III complies with the requirements of NEN 2443:2013, the Dutch standard for parking and storing passenger cars in garages. It also meets the following certification standards: EMC 89/336/EEC, 73/23/EEC, EN61000-6-3+A11, EN61000-6-2, EN61000-3-2, and EN61000-3-3+A1.
In addition to gas detection in parking and storage garages, the system can also be used for other applications, such as schools, food and refrigerant monitoring, and various light industrial environments.
More Information
| Dimensions (l x w x h) | 400x340x160 mm |
|---|---|
| Initial signals | RS 485 serial connection |
| Detector power supply | 10 - 32 V dc |
| Absorbed power | 8 Watt |
| Module relay | Voltage via reading unit |
| Signal processing unit power supply | 12 - 24 Vdc |
| Accuracy | ±2 % measuring range ±1 |
| repeatability | ±2 % measuring range ±1 |
| Storage temperature | –20°C - +75°C |
| Display | Graphical TFT |